Burner Control Unit PFU 760 - DISCONTINUED
- For directly ignited burners of unlimited capacity in intermittent operation or in continuous operation pursuant to EN 746-2
- Plug-in function unit for mounting in 19″ module subracks
- Flame control by UV, ionization, or by using the furnace chamber temperature
- Display of the program status, unit parameters and flame signal; manual mode for burner adjustment and for diagnostic purposes
- Programming and diagnostic software BCSoft simplifies logistics management
- Air valve control relieves the furnace control
- Connection to PROFIBUS-DP via field bus interface PFA 700
- FM approved
- Explore our limited stock of hard-to-find models

This product has been discontinued by the manufacturer and is no longer available. Please Contact Us to discuss options for replacement, or See Below for information regarding alternative products from this manufacturer and others.
Learn More:
Description Documentation Ordering Information Accessories
|
||||||||||
| Model and Description | Stock | Price | Cart | |||||||
| PFU 760T PFU 760T |
||||||||||
| PFU 760LN PFU 760LN |
||||||||||
Description
The burner control unit PFU 760 controls, ignites, and monitors gas burners for intermittent or continuous operation. Its fully electronic design reacts quickly to various process requirements and is therefore suitable for frequent cycling operation.
The PFU 760 can be used for directly ignited industrial burners. The burners can be modulating or stage-controlled.
On industrial furnaces, the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner, for example, it ensures that the burner always ignites in a safe condition after it has been restarted.
The burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners.
The air valve control on the burner control unit PFU 760L assists the furnace control for cooling, purging, and capacity control tasks.
The program status, the unit parameters, and the level of the flame signal can be read directly from the unit. The burner can be controlled manually for commissioning and diagnostic purposes.
If the local requirements on the burner control unit change, the PC software BCSoft can be adjusted to the unit parameters of the application using the optical interface.
Users can see input and output signals and the error history.
Kromschröder has discontinued manufacture of their PF-19 equipment. If you’re in the market for spare parts, please Contact Us .
While we are no longer stocking these components, we may be able to source spares for you. Likewise, if you’re looking for upgrade options, please gather as much information as you can (especially electrical prints, showing the PF-19 rack system wired-in), and Contact Us for options.
Documentation
Accessories
| Model and Description | Price | Cart |
| PCO 200 Optical Adapter for BC Soft with USB interface, includes CD-ROM |
Contact Us | Not available for online purchase. |