UV Detector UVS 10The UVS UV detector monitors gas burners of unlimited capacity with or without fan, on hot-air furnaces, gas-fired boilers, industrial furnaces and excess-gas flaring installations in conjunction with the PFU 780 burner control, the PFU 760 burner control, the IFS 110IM burner control or BCU series automatic burner controls.

Features

  • The UV sensor monitors the gas burners in intermittent operation
  • The burners can either be ignited directly or operated as pilot and main burners
  • Suitable for small burners due to high sensitivity
  • Virtually immune to interference due to its insensitivity to daylight, infrared radiation and incandescent bulbs
  • Maximum safety thanks to protection against discontinuity or short-circuit on the flame signal cable
  • Lower logistics costs as the UVS 10 replaces several previous models
  • Suits industrial needs due to robust design
  • Complies with the requirements of EN 298 in conjunction with Elster Kromschroder automatic burner control units
  • UV sensors UVS 1, UVS 6 and UVS 8 can be replaced by using various adapters
Documentation for UVS UV Detector

Documentation

Manufacturer's Product Brochure
Manufacturer's Operating Instructions
Manufacturer's Technical Information

 
Ordering information for UVS UV Detector

Ordering Information

Model Description Price
(US List)
Order Now
UVS 10D2 1/2" NPT internal thread. Replaces UVS 8T. $157 Buy the UVS UV detector
UVS 10D3 1/2" NPT internal thread and cooling air connection. $167 Buy the UVS UV detector
UVS 10D0G1 Rp 1/2" internal thread and M20 cable gland. Replaces UVS 6. $162 Buy the UVS UV detector
UVS ACC 01 Replacement UV Tube for UVS 1, 6, 10. $111 Buy the UVS UV detector
 
Applications for UVS UV Detector

Applications

Click on images for close-up view.

Application for UV detectors UVS Features

The UV detector responds to the ultraviolet light of a flame. It does not react to daylight, incandescent lamps, infrared radiation, hot work-pieces or incandescent furnace walls.

The UVS 6 is complete with a quartz lens, which isolates the detector from the hot furnace atmosphere against humidity, dirt and heat.

A quartz lens is not necessary for the UVS 8 detector. Overheating, dirt and condensation can be avoided with cooling as shown in the diagram below.

Max lead length between UV detector and automatic burner control is 150 feet (50 m), if plastic conduit is used. If metallic conduit is used, this length should not exceed 50 feet (15 m).

The maximum recommended sighting distance between the UV detector and the flame is 16" (400 mm)
 
Specifications for UVS UV Detector

Specifications

General Specifications
Materials of construction: Aluminium housing with integrated heat
guard, with connection terminals
Distance between UV sensor and flame: 300 – 400 mm.
UV tube: P578, spectral range: 190 – 270 nm
max. sensitivity: 210 nm ± 10 nm
Service life of the UV tube: approx. 10,000 operating hours
Min. DC signal: 1 μA
Enclosure: IP 65
Ambient temperature: -40 to +80°C (-40 to +176°F)
Weight: 280 g (0.6 lbs)
Max. length of cable UV sensor – automatic burner control unit: see instructions for automatic burner control unit