Combustion 911
Supplying and Serving the Combustion Industry
Phone: 330-678-8220
Email: support_ab

Flame Relay PFF 704Flame Relay PFF 704

The PFF 704 Flame Relay is designed to detect and signal an existing gas flame using flame rod or UV detector. For use with multi-burner control on burner control units PFU 760 or where automatic monitoring is not required.

The PFF 704 has four independent flame amplifiers. When a flame is present the amplifier energizes a relay. The contacts of this relay can be used for control functions.

Features

  • For flame detection
  • For multi-burner control
  • Flame monitoring with flame rod or UV detector
  • Four independent flame amplifiers
  • Single-electrode operation possible
  • FM approved
Documentation for PFF 704 Flame Relay

Documentation

Manufacturer's Product Brochure
Manufacturer's Operating Instructions

 
Ordering information for PFF 704 Flame Relay

Ordering Information

Model Description Price
(US List)
Order Now
PFF 704T/N 19" module for use with multi-burner control on burner control units PFS 778 or where automatic monitoring is not required. $457 Buy the PFF 704 Flame Relay
 
Applications for PFF 704 Flame Relay

Applications

Click on images for close-up view.

Application for Flame Relay PFF 704 Multi-burner control involves the joint control of several burners.

One burner control unit is responsible for the entire control function and also monitors the first burner. Flame relays monitor the other burners in this group.

If a flame monitored by the PFF 704 goes out during operation, a signal to the automatic control is interrupted and all other burners are switched off immediately. If an outside light is detected before the ignition (no flame check), the system goes to lockout.

The drawing shows an example with flame rod. UV monitoring or single-electrode operation is also possible.
 
Specifications for PFF 704 Flame Relay

Specifications

General Specifications
Power consumption: 10 VA
Ionization voltage: 230 V AC
Max. length of flame signal cable: 300 ft (100m)
Cut-off sensitivity of flame amplifier: 1 μA - 10 μA (set at factory at 1 μA) Fine-wire fuse 2.8 A, fast blowing, acc. to UL.
Weight: approx. 1.1 lbs (0.51 kg).