Combustion 911
Supplying and Serving the Combustion Industry
Phone: 330-678-8220
Email: support_ab

Burner Control Unit BCU 370

Burner Control Unit BCU 370The BCU (burner control unit) 370 controls, ignites, and monitors industrial forced air burners of unlimited capacity in intermittent or continuous operation. It can be used for directly ignited forced air burners or forced air burners ignited with a pilot burner. The burner control unit activates the blower and sets the connected butterfly valve to the pre-purging and ignition position. After the pre-purge and burner start, an enable signal is sent to an external controller that positions the butterfly valve according to the output demand. Post-purge occurs after the end of the burner operation. The BCU 370 monitors the gas and air pressure, an integrated tightness control function (optional) checks the valves with an external gas pressure switch.

The quick-start option allows standard-compliant start-up of a forced air burner without pre-purge after normal shutdown. This means unnecessary air won’t get into the combustion chamber. The heat output is available as quickly as possible after a temperature demand.

The program status, the unit parameters, and the level of the flame signal can be read directly from the unit. An integrated manual mode allows you to start a burner and set the butterfly valve position independently of the central control system. The BCSoft operator-control and setting software provides a powerful tool for start-up and servicing.

To reduce the installation and wiring costs, Kromschroder offers an optional Profibus-DP interface to transfer the activation signals and feedback

View the Animation (flash required)

Features

  • Modulation of forced air gas burners of unlimited capacity in intermittent or continuous operation
  • Control of fan and butterfly valves
  • Simple system set-up with optional tightness control and integrated ignition unit
  • Easy start-up and maintenance in manual operating mode
  • Enhanced flexibility and simplified logistics with programmable functions
  • Easy servicing with user-friendly operating, warning, and fault messages
  • Available with optional integral field bus interface for simple wiring
  • EC type-tested and certified, CSA and FM approved
Documentation for Burner Control Unit BCU 370

Documentation

Manufacturer's Product Brochure
Manufacturer's Operating Instructions
Manufacturer's Technical Sheet

 
Ordering information for for Burner Control Unit BCU 370

Ordering Information

Model Description Price
(US List)
Order Now
BCU 370QFEU0D1 Without ignition; Mains voltage: 120 V AC, 50/60 Hz $572 Buy the BCU 370 Burner Control
BCU 370QI1FEU0D1 Electronic ignition, single-pole; Mains voltage: 120 V AC, 50/60 Hz $702 Buy the BCU 370 Burner Control
BCU 370QI1FEU0D1B1 Electronic ignition, single-pole, and ProfiBUS-DP; Mains voltage: 120 V AC, 50/60 Hz $927 Buy the BCU 370 Burner Control
BCU 370QFEU0D3B1-3 With tightness control, ProifiBUS-DP and butterfly valve control over ProfiBUS; Mains voltage: 120 V AC, 50/60 Hz $1200 Buy the BCU 370 Burner Control
BCU 370WFEU0D1 Without ignition; Mains voltage: 230 V AC, 50/60 Hz $611 Buy the BCU 370 Burner Control
For all other configurations Contact Combustion 911

Accessories

Model Description Price
(US List)
Order Now
BCU OPTO Opto-adapter (serial port connection) includes BCSoft CD-ROM $284 Buy the optical adapter
 
Applications for Burner Control Unit BCU 370

Applications

Click on images for close-up view.

Application for BCU 370 Burner Control Unit Modulating-controlled forced draught burner

The BCU 370 controls the blower and moves the butterfly valve to pre-purging and ignition position. It issues the Enable signal to the control system after start-up of the burner.
Application for BCU 370 Burner Control Unit Modulating-controlled forced draught burner with tightness control

In addition to controlling the forced draught burner, the burner control unit also monitors the fail-safe function of the two solenoid valves for gas via the DG gas pressure switch.
Application for BCU 370 Burner Control Unit Modulating-controlled forced draught burner with pilot burner and tightness control

A pilot burner ignites the main burner and is switched off during the main burner’s safety time.
 
Specifications for Burner Control Unit BCU 370

Specifications

Electrical
Mains voltage: 120 V AC, -15/+10%, 50/60 Hz, for grounded or ungrounded mains.
Power consumption: Approx. 9 VA plus approx. 50 VA for integrated ignition
Voltage to inputs, valves, fan, controller enable, actuator and ignition unit: mains voltage
Flame control with UV sensor or ionisation sensor: Ionisation control: 1 – 28 µA
UV control: 1 – 35 µA
Input voltage signal inputs: Signal "1": 80-126.5 V
Signal "0": 0-20V
Input current signal "1": Typ. 2 mA
Output to ignition transformer: No-switch contacts via semi-conductor
Max. number of operating cycles: 250,000
   
Contact Ratings
Valves: Max. 1 A, cos φ = 1
Butterfly valves: Max. 1 A, cos φ = 1
Ignition: Max. 1 A, cos φ = 0.3
Controller enable signal: Max. 1 A, cos φ = 1, the contacts may be loaded with a max. total of 2.5 A
Fan: Max. 3 A, start-up current: Max. 6.5 A < 1 s.
The outputs may be loaded with a max. total of 4 A.
Operation and fault signalling contacts: Dry Contact, max. 1 A, 253 V, not fused internally
Reset/Information button: Max. number of operating cycles: 1000
Fuse in BCU, replaceable, F1: T 5A H, pursuant to IEC 60127-2/5
Permissible UV sensors: Elster Kromschroder models UVS 1, 5, 6, 8 and UVD 1
   
Operation and Environment
Maximum length of ignition cable with integrated electronic ignition: 1 m
Maximum length of ionisation/UV cable: 50 m (164 ft)
Ambient temperature: BCU 370: -20 – +60 °C (-4 – +140 °F)
BCU 370..I: -10 – +60 °C (14 – +140 °F)
no condensation permitted
   
Construction Materials
Enclosure: IP 54 pursuant to IEC 529
Housing: impact-resistant and heat-resistant plastic
Upper section: Plug-in upper section with operating and display elements
Lower section: connection terminals, earthing strip and prewired neutral bus with spacious wiring chamber
Connections: 1x M25 multiple screw connector, 4x 7 mm cable grommets.
2x M20 multiple screw connectors, 2x 7 mm cable grommets, and loosely enclosed.
1x or 2x M16 plastic screw connector(s) for the ignition cable(s).
Weight: Approx. 1.8 kg (4 lbs.)