90 PSI Safety Shut-Off Valves with Proof of Closure

90 PSI version
90 PSI VMR

Elektrogas offers a high pressure, 90 PSI, version of their safety shut-off solenoid valves (SSOVs) with proof of closure. The valve body is made with a solid aluminum alloy die cast with a wide range of NPT thread and ANSI connections.

The VMx series are normally closed SSOVs. When no power is present, the spring, along with the inlet gas pressure, keeps the valve sealed tightly.

The 90 PSI version is a piloted valve. When power is applied, the pilot valve is opened using the electromagnet. The inlet pressure of the gas is used to open the main valve. VMR is fast opening and fast closing. VML is slow opening and fast closing. The slow opening behavior is thanks to a dampener (oil brake) which decreases the rate at which the valve is allowed to open. The opening speed for VML is variable.

90 PSI models are recommended for main gas trains and burner gas trains where extremely high cycle counts are not expected.

Proof of Closure

Elektrogas’s proof of closure device incorporates a two-tone LED in the DIN plug. This is important because whenever code requires the use of proof of closure, visual indication is also mandatory. Using a two-tone LED is necessary because code states you must use a different light to signal each state (open/closed) — it is not permitted for the absence of a illumination to signal either state, because this could provide false information in the case an LED has failed.

In systems where proof of closure is not required, you may still need visual indication. For these situations, Elektrogas offers a mechanical visual indicator (VI), which is sold and ships separately. All non-POC valves are prepared for the VI

The 90 PSI version is not listed on Combustion 911, but is available. Please contact us for more information!

For Automation

Please visit olstrad.com to learn more about our automation processes!

Posted by  b-olstrad ; Published March 9, 2022

 Categories: Elektrogas, Industrial Solenoid Valves, Industrial Valves



 Bookmark the permalink

 RSS Feed (comments for this post)

Both comments and trackbacks are currently closed.

 
 

Combustion 911

600 Mogadore Rd. Kent, OH 44240

Phone 330-678-3683

Email: support_ab@combustion911.com

View Terms and Conditions

Privacy Policy

©2021 Olstrad Engineering All Rights Reserved

Visit Combustion 911 on LinkedInVisit Combustion 911 on FacebookVisit Combustion 911 on TwitterWatch Combustion 911 videos on YouTubeEmail Combustion 911Read Articles on the Combustion 911 Blog

Need a quote? Have a Question?