SubTotal: 
  
Combustion 911
Supplying and Serving the Combustion Industry
an Olsträd Engineering Company

Site Search

Learn More About...

Automatic Burner Control Unit IFD 258

Burner Control IFD 258-10/2Q

Price:
Quantity:
  • Mains voltage: 120 V AC, 50/60 Hz
  • 2-second safety time during operation
  • 10-second trial for ignition period
  • Continuous self-testing for faults
  • Immediate fault lock-out or restart following flame failure available as a switchable function
  • Flame control with UV sensor or ionization sensor
  • Diverse installation possibilities via holes or snap mechanism for DIN rail
  • Display for program status and flame signal intensity
  • CSA, CE, AGA approvals

Accessories

Model and Description Price Cart
Ignition Cable
Silicon Rubber Cable High Voltage 7mm (priced per foot).
Also see: UVS, TGI, and TZI

Applications

Click on images for close-up view.

Application for Automatic Burner Control IFD 258 Forced draught burners
Control: On/Off

Gas valve and air valve are activated simultaneously. The burner is ignited and monitored by a single electrode. In the event of a flame failure, an immediate fault lock-out occurs.
Application for Automatic Burner Control IFD 258 Two-stage-controlled burner
Control: ON/OFF or ON/HIGH/LOW/OFF

The burner BIO/BIC starts at low-fire rate. Once the normal operating state is reached, the automatic burner control unit for continuous operation IFD 258 will release control. The PLC can now pulse the air solenoid valve VR..R in order to control the capacity between high and low fire.
Application for Automatic Burner Control IFD 258 Modulating-controlled burner
Control: ON/OFF/continuous

The PLC uses the actuator IC 20 to move the air butterfly valve BVA to ignition position. The burner BIO/BIC starts at low-fire rate. Once the normal operating state is reached, the PLC uses the actuator IC 20 and the air butterfly valve BVA to control the burner capacity.

Specifications

General Specifications
Operating voltage: 120 V AC, -15/+10%, 50/60 Hz
Safety time on start-up: 10 sec.
Safety time during operation: < 1sec. < 2 sec.
Ignition time: approx. 2, 3 or 6 sec
Power consumption: approx. 9 VA
Output voltage for valves and ignition transformer: mains voltage
Ignition output: max. 2 A, cos φ = 0.2
Valve output: max. 1 A, cos φ = 1
Signalling contacts: max. 2 A, 253 V AC
Max. number of operating cycles: 250,000
Max. number of operating cycles for Reset button: 1000
Max. number of operating cycles for Mains button: 1000
Signal inputs (110/120 V AC): Signal "1": 80 - 126.5 V
Signal "0": 0 - 20 V
Frequency: 50/60 Hz.
Input current signal inputs: Signal "1": typ. 2 mA.
Flame control sensor voltage: approx. 230 V AC
Flame control sensor current: > 1 µA
Flame control Max. sensor current: ionization < 28 µA.
Ignition cable: IFD 258: max. 5 m, recommended < 1 m (with TZI/TGI)
Permissible UV sensors: Elster Kromschröder models UVS for ambient temperatures from -40 to +80°C (-40 to 176°F)
Valve connections: 1
Ignition current: 25 mA
Spark gap: 2 mm, max. 5 mm
Fuse in unit: F1: T 3.15A H 250 V pursuant to IEC 127-2/5
Ambient temperature: -20 to +60°C (-4 to +140°F)
Relative humidity: no condensation permitted
Enclosure: IP 54 pursuant to IEC 529. Overvoltage category III pursuant to EN 60730
Cable gland: M16
Installation position: any
Weight: 610 g (1.34 lbs.)

Jump to IFD 258 model page

Model:

Click Here for Help choosing which IFD 258 Burner Control you need.
(Click here to Close)

Select desired characteristic

All Products
3 sec. Trial
5 sec. Trial
10 sec. Trial
IFD 258-3/2Q
Price:
Description: Mains Voltage: 120 V AC, 50/60 Hz; Safety time during operation: 2 seconds; Trial for Ignition Period: 3 seconds.
IFD 258-5/2Q
Price:
Description: Mains Voltage: 120 V AC, 50/60 Hz; Safety time during operation: 2 seconds; Trial for Ignition Period: 5 seconds.
IFD 258-10/2Q
Price:
Description: Mains Voltage: 120 V AC, 50/60 Hz; Safety time during operation: 2 seconds; Trial for Ignition Period: 10 seconds.

Latest Blog Post

  • Use the ZI-808 From the Internet
    One of the most exciting features of the ZI-808 is its built-in web server. Its user interface is designed like a standard web page and embedded into the instrument. That means that any device that can open a web page can use it. Desktop, laptop, tablet, smart phone, Android, Windows, iOS, Linux, Edge, IE, Chrome, Firefox. read full post
Combustion 911 Blog Blog Home   Combustion 911 RSS Feed RSS feed
Top