% Fuel Lost to Heat Excess & Tramp Air to Flue Temp
O2 %/vol (Dry Basis) %Excess Air Furnace Flue Temperature(°F)
1,400 1,500 1,600 1,700 1,800 1,900 2,000 2,100 2,200
2.2% 10.0% 2.4% 2.6% 2.8% 3.0% 3.1% 3.3% 3.5% 3.7% 3.8%
3.1% 15.0% 3.7% 3.9% 4.2% 4.4% 4.7% 5.0% 5.2% 5.5% 5.8%
4.0% 20.0% 4.9% 5.2% 5.6% 5.9% 6.3% 6.6% 7.0% 7.3% 7.7%
4.7% 25.0% 6.1% 6.5% 7.0% 7.4% 7.8% 8.3% 8.7% 9.2% 9.6%
5.4% 30.0% 7.3% 7.8% 8.4% 8.9% 9.4% 9.9% 10.5% 11.0% 11.5%
6.1% 35.0% 8.5% 9.2% 9.8% 10.4% 11.0% 11.6% 12.2% 12.8% 13.4%
6.7% 40.0% 9.8% 10.5% 11.2% 11.9% 12.6% 13.3% 14.0% 14.7% 15.3%
7.2% 45.0% 11.0% 11.8% 12.6% 13.3% 14.1% 14.9% 15.7% 16.5% 17.3%
7.7% 50.0% 12.2% 13.1% 14.0% 14.8% 15.7% 16.6% 17.4% 18.3% 19.2%
8.2% 55.0% 13.4% 14.4% 15.3% 16.3% 17.3% 18.2% 19.2% 20.1% 21.1%
8.6% 60.0% 14.7% 15.7% 16.7% 17.8% 18.8% 19.9% 20.9% 22.0% 23.0%