Flame Detector IFW15The Flame Relay IFW 15 detects and signals an existing flame using flame rod or UV-detector. Use it for multi-burner control together with the IFS 110 IM automatic burner control or wherever a fully automatic control is not required.

Features

  • For signaling flame
  • For multi-burner control during intermittent operation in conjunction with automatic burner control IFS 110 IM
  • UV-detector or ionization control with flame rod
  • Potential free contacts
  • Integrated "ON" lamp
  • FM approved

 

Documentation for Flame Relay IFW 15

Documentation

Manufacturer's Product Brochure
Manufacturer's Operating Instructions

 
Ordering information for Flame Relay IFW 15

Ordering Information

Model Description Price
(US List)
Order Now
IFW 15T-N Flame relay used to detect and signal an existing flame using flame rod or UV-detector. $218 Buy the IFW15 Flame Relay
 
Applications for Flame Relay IFW 15

Applications

Application for Flame Relay IFW 15 Flame control with flame rod

An alternating voltage is applied between the flame rod, which projects into the flame, and the grounded burner. As soon as the flame is established a small current flows through it and is rectified by the flame. The electronic amplifying stage detects only this direct current signal which, after amplification, is used to energize a relay. A flame cannot be simulated.
Application for Flame Relay IFW 15 Flame control with UV-detector

The UV-detector mainly consists of a tube which is sensitive to light and of electronic components. The tube responds to the ultra violet (UV) radiation from a gas flame, it does not react to sunlight and light from filament lamps.
 
Specifications for Flame Relay IFW 15

Specifications

General Specifications
Operating voltage: 110 VAC/120 VAC + 10/-15%, 50/60 Hz
Power consumption: 12 VA
Output voltage for ionization sensor: 220 VAC
Sensor current: > 1 µA DC
Output signal: Potential free contacts, one NC, one NO contact
Contact rating: max. 2 A
Flame signal: lamp in device
Ambient temperature: -4 °F to 140 °F (-20 °C to +60 °C)
Cable gland: Five openings for external wire connection
Terminals: 2 × AWG 16 (2 × 1.5 mm2)
Mounting position: any